VAV / CAV system solution for energy-optimised fan regulation for room ventilation applications |
 |
 |

Control of frequency converter-controlled supply/exhaust fans based on the damper position of the connected VAV/CAV units
|
 |
| Application area |
 |
Comfort zone, industrial zone * |
 |
 |
 |
| VAV controllers |
 |
Connection via MP-Bus |
 |
VAV-Compact, VRP-M system solution |
 |
| Control |
 |
Via VAV-Compact sensor connection function, 0…10 V, 2…10 V, MP-Bus |
 |
|
 |
| VAV application |
 |
CAV steps [CLOSED / V’min / V’max] |
 |
VAV control range [CLOSED / V’min…V’max] |
 |
| Supply |
 |
AC / DC 24 V |
 |
|
 |
| Output |
 |
Frequency converter |
 |
0…10 V with limiting function |
|
|
 |
|
 |
Cascade |
 |
0…10 V |
 |
| Input |
 |
Override control |
 |
OFF / AUTO / Emergency mode |
|
|
 |
|
 |
Cascade signal |
 |
Expansion of system size |
 |
| Diagnostics, settings |
 |
Display, menu-guided |
 |
Configuration, operating data, error list |
 |
| VAV controller operation |
 |
Display, menu-guided |
 |
Volumetric flow, damper position, V’min and V’max setting |
|
|
 |
|
 |
RJ11 connection |
 |
for Belimo PC-Tool |
 |
| * according to the application area of the VAV controller |
|
 |

| Application |
 |
Function |
 |
Controller type |
 |
Signal type |
 |
Setpoint input (connection) |
 |
Remark |
 |
 |
| CAV |
 |
Steps CLOSED / V’min / V’max |
 |
2-point output |
 |
Switch, presence detector |
 |
VAV-Compact sensor connection |
 |
DC 24 V supply required |
 |
 |
| VAV |
 |
CLOSED / V’min …. V’max |
 |
CR24-B1 / -B2 / -B3 |
 |
Belimo VAV system output 0/2…10 V |
 |
VAV-Compact sensor connection |
 |
|
 |
 |
| VAV |
 |
CLOSED / V’min …. V’max |
 |
CR24-B1 / -B2 / -B3 |
 |
Belimo VAV system output 0/2…10 V |
 |
Analog input [Ain 2…10V] |
 |
|
 |
 |
| VAV |
 |
V’min…V’max |
 |
Room temperature controller, DDC, PLC with analog output |
 |
0…10 V or 2…10 V |
 |
Analog input [Ain 0…10V / 2…10V] |
 |
|
 |
 |
| VAV |
 |
CLOSED / V’min…V’max |
 |
DDC, PLC with MP-interface |
 |
MP-Bus |
 |
MP |
 |
|
 |
 |

Copyright (c)2013 BELIMO Automation AG. All rights reserved.