 | Power supply |
|
 |
AC 24 V / 50/60 Hz |
 |
 |
 |
|
 |
 |
 |
 |
 | Application |
|
 |
Air volume or room temperature control in the comfort zone |
 |
 |
 |
|
 |
 |
 |
|
 |
Internal temperature sensor (Type NTC, sensing range 10 … 45°C) |
 |
 |
 |
|
 |
 |
 |
|
 |
Setpoint (adjustment range 30 … 70% air / 15 … 36°C temperature) |
 |
 |
 |
|
 |
 |
 |
 |
 | Operation |
|
 |
Mode selection switch: COMF – MIN – MAX |
 |
 |
 |
|
 |
 |
 |
|
 |
Mode indication LEDs: COMF – MIN – MAX |
 |
 |
 |
|
 |
 |
 |
|
 |
Setpoint adjustment: Rotary knob (CRA24-B3P covered): 30 … 70% air / ±3 K temperature |
 |
 |
 |
|
 |
 |
 |
 |
 | 4 inputs |
|
 |
Kitchen override function |
 |
 |
 |
|
 |
 |
 |
|
 |
Bathroom override function |
 |
 |
 |
|
 |
 |
 |
|
 |
Energy hold-off (EHO) |
 |
 |
 |
|
 |
 |
 |
|
 |
External temperature sensor (Type NTC 5 kΩ, sensing range 10 … 45°C) |
 |
 |
 |
|
 |
 |
 |
 |
 | 3 outputs |
|
 |
2 … 10 V system output for supply air: Belimo VAV controller, damper actuator |
 |
 |
 |
|
 |
 |
 |
|
 |
2 … 10 V system output for exhaust air: Belimo VAV controller, damper actuator |
 |
 |
 |
|
 |
 |
 |
|
 |
Heating output: 2-point (thermal actuator) / 3-point |
 |
 |
 |
|
 |
 |
 |
 |
 | Functions |
|
 |
Control characteristic: P |
 |
 |
 |
|
 |
 |
 |
|
 |
P-band, switchable |
 |
 |
 |
|
 |
 |
 |
|
 |
Switchable control strategy ( air volume / room temperature) |
 |
 |
 |
|
 |
 |
 |
|
 |
Switchable air sequence (cooling / heating) |
 |
 |
 |
|
 |
 |
 |
|
 |
Room temperature monitoring (min and max) |
 |
 |
 |
|
 |
 |
 |
|
 |
Internal function test, including nominal voltage test |
 |
 |
 |
|
 |
 |
 |
|
 |
Commissioning mode with output and sequence simulation |
 |
 |
 |
|
 |
 |
 |
|
 |
Tool connection (ZTH-GEN, PC-Tool) for VAV controller diagnostics |
 |
 |
 |
|
 |
 |
 |
 |
 | Mounting |
|
 |
Surface mounting with flush-mounted or surface-mounted connection |
 |
 |
 |
|
 |
 |
 |
 |
 | Additional documentation |
|
 |
Comprehensive and regularly updated documentation with descriptions of specific applications is available for the CRA24-3(P) controller. |
 |
 |
 |
|
 |
 |
 |